On/Off valve for electrical remote control stepwise working - closed without current

1795007000 On/off valve for electrical control - closed without current DN 1 1/2" PN 10/16

Components

  • 1: Main valve
  • 2: Ball valve (A, B)
  • 3: Filter
  • 4: Throttle check valve (A, B)
  • 5: Electric solenoid valve (A, B)
  • 6: Pressure gauge with ball valve
  • 7: Vent plug
On/off valve for electrical control - closed without current DN 1 1/2" PN 10/16
1795007000
Add to an existing list

Product attributes
DN 1 1/2"
PN 16 bar
L 210 mm
weight 10.000 kg
Availability on demand

Physical characteristics

  • The main valve is a hydraulically operating diaphragm valve. The work energy is the inherent medium.
  • Most valve types operate purely hydraulically without any foreign energy.

Application

  • To use in drinking water systems (other media after consultation)
  • Slow, step–by–step opening or closing of a supply system by means of electrical impulses
  • Regulation of water levels in the reservoir (regulation of the inflow or outflow in the reservoir)
  • Regulation of the flow rates
  • Regulation of the flow rates for cooling circuits (in conjunction with a temperature switch)

Mode of operation

  • The open/close valve for the electric actuation opens or closes step–by–step depending on the respective actuation of the solenoid valve. The valve closes when the solenoid valves are de–energised. The opening and closing speeds can be set on the throttle non–return valve.

Product information

  • To calculate the dimensions of the valve please refer to the following information:
  • Maximum and minimum inlet pressure (static and dynamic pressure ratios)
  • Existing counterpressure
  • Required flow rate
  • Maximum permissible loss of pressure
  • Voltage information for the solenoid valve
  • Available line diameters and lengths
  • Construction of the valve (straight or angle design)
  • For the calculation basis, information on the loss of pressure and the characteristic values of the valve, please refer to the end of Chapter E.

Design

  • Design according to DIN EN 1074
  • Construction length acc. to DIN EN 558
  • Flange mass according to DIN 1092-2, to PN 25 DN 300
  • Pressure levels: PN 10 or PN 16 to DN 300, PN 25 to DN 200, higher pressures on request.
  • Nominal widths DN 50, DN 80, DN 100 and DN 150 available in angular design
  • Nominal widths 1 ½" and 2" with threaded connection (female thread)
  • Medium temperature up to 40°C

Installation and assembly

  • Shut–off valves should be fitted on both sides of the valve and a dirt trap should be installed on the inlet side of the valve. Depending on the installation situation, a mounting/dismounting adapter should be provided.

Vantages

  • Maintenance-free, non-rusting valve seat
  • Pressed-in seat
  • EWS-coating according to RAL GSK
mehr