Pressure reducing valve for electrical control - closed without current

1503 Pressure reducing valve for electrical control - closed without current

Components

  • 1: Main valve
  • 2: Ball valve (A, B, C)
  • 3: Filter
  • 4: Orifice
  • 5: Throttle check valve (A, B)
  • 6: Control valve
  • 7: Manometer with ball valve (A, B)
  • 8: Optical position indicator (optional: Electrical position indicator, opening limiter)
  • 9: Electric solenoid valve
Article No. DN PN
(bar)
L
(mm)
weight
(kg)
Availability Watchlist
1503007000 1 1/2" 16 210 11.000 on demand
DRV for electrical control - closed without current DN 1 1/2" PN 10/16
1503007000
Add to an existing list

1503008000 2" 16 210 11.000 on demand
DRV for electrical control - closed without current DN 2" PN 10/16
1503008000
Add to an existing list

1503040000 40 16 200 15.750 on demand
DRV for electrical control - closed without current DN 40 PN 10/16
1503040000
Add to an existing list

1503050000 50 16 230 16.250 on demand
DRV for electrical control - closed without current DN 50 PN 10/16
1503050000
Add to an existing list

1503065000 65 16 290 21.300 on demand
DRV for electrical control - closed without current DN 65 PN 10/16
1503065000
Add to an existing list

1503065025 65 25 290 21.450 on demand
DRV for electrical control - closed without current DN 65 PN 25
1503065025
Add to an existing list

1503080000 80 16 310 27.400 on demand
DRV for electrical control - closed without current DN 80 PN 10/16
1503080000
Add to an existing list

1503080025 80 25 310 27.400 on demand
DRV for electrical control - closed without current DN 80 PN 25
1503080025
Add to an existing list

1503100000 100 16 350 35.400 on demand
DRV for electrical control - closed without current DN 100 PN 10/16
1503100000
Add to an existing list

1503125000 125 16 400 51.500 on demand
DRV for electrical control - closed without current DN 125 PN 10/16
1503125000
Add to an existing list

1503150000 150 16 480 76.000 on demand
DRV for electrical control - closed without current DN 150 PN 10/16
1503150000
Add to an existing list

1503200000 200 10 600 114.600 on demand
DRV for electrical control - closed without current DN 200 PN 10
1503200000
Add to an existing list

1503200016 200 16 600 114.600 on demand
DRV for electrical control - closed without current DN 200 PN 16
1503200016
Add to an existing list

1503250000 250 10/16 730 247.000 on demand
DRV for electrical control - closed without current DN 250 PN 10/16
1503250000
Add to an existing list

1503300000 300 10/16 850 356.000 on demand
DRV for electrical control - closed without current DN 300 PN 10/16
1503300000
Add to an existing list

Physical characteristics

  • The main valve is a hydraulically operating diaphragm valve. The work energy is the inherent medium.
  • Most valve types operate purely hydraulically without any foreign energy.

Application

  • To use in drinking water systems (other media after consultation)
  • Reduction in pressure for a network feed with a reservoir as the water level control
  • Controlled emergency feed into a second network (network connections)
  • In combination with an orifice plate for filling the reservoir

Mode of operation

  • The pressure reducing valve for an electrical actuation reduces a variable inlet pressure to a constant outlet pressure when the solenoid valve is energised. The valve is shut when the power is off. Fluctuating inlet pressure and flow rate have no effect on the outlet pressure controlled by the control valve. The outlet pressure is adjustable in the range from 1.5 to 12 bar (standard design). The opening and closing speeds can be set independently.

Product information

  • To calculate the dimensions of the valve please refer to the following information:
  • Maximum and minimum inlet pressure (static and dynamic pressure ratios)
  • Required outlet pressure.
  • Maximum and minimum flow rates
  • Possible requirement for extinguishing water
  • Available line diameters and lengths
  • Voltage information for the solenoid valve
  • Construction of the valve (straight or angle design)
  • For the calculation basis, information on the loss of pressure and the characteristic values of the valve, please refer to the end of Chapter E.

Design

  • Design according to DIN EN 1074
  • Construction length acc. to DIN EN 558
  • Flange mass according to DIN 1092-2, to PN 25 DN 300
  • Pressure levels: PN 10 or PN 16 to DN 300, PN 25 to DN 200, higher pressures on request.
  • Nominal widths DN 50, DN 80, DN 100 and DN 150 available in angular design
  • Nominal widths 1 ½" and 2" with threaded connection (female thread)
  • Medium temperature up to 40°C

Installation and assembly

  • Shut–off valves should be fitted on both sides of the valve and a dirt trap should be installed on the inlet side of the valve. Depending on the installation situation, a mounting/dismounting adapter and an aeration and ventilation system should be provided.

Vantages

  • Maintenance-free, non-rusting valve seat
  • Pressed-in seat
  • EWS-coating according to RAL GSK
mehr
  1. Watchlist
  2. Contact
    1. DE